There are two ways to carry out the stopping DC braking: parameter setting and digital
input. DC-braking will only be activated, when
● a stop command is active, and
● [b1.40]=0, and
● output frequency≤[b1.41], and
● digital input “Stopping DC-braking enabled” is active, or [b1.42]>0.